MCD3000 Series
MG.15.A4.22 - VLT is a registered Danfoss trademark 9
Installation
line contactor or shunt trip activated circuit breaker
must be used to totally isolate the motor in the event
of a fault condition.
When fitted with one of the kits from the following
table, MCD3000 units are inside delta capable. The
inside delta capability is additional to all normal
functionality and is totally automatic. No user
adjustment or settings are required.
MCD3000 Model Inside Delta Kit
MCD3185 175G3043
MCD3220 175G3044
MCD3300 175G3045
MCD3315 175G3046
MCD3400 175G3047
MCD3500 175G3048
MCD3600 175G3049
MCD3700 175G3050
MCD3800 175G3051
Control Supply Voltage
Voltage must be connected to the starter control
voltage terminals. Control voltage can be either 230
VAC or 400 VAC (CV4)
Electr oni cs
S uppl y
A3
A2
A1
110 VAC (+ 10 % / - 15 % )
or 230 VAC (+10% / -15%)
{
{
MCD3000 Model Maximum VA
MCD3007~MCD3022 10VA
MCD3030~MCD3055 17VA
MCD3075~MCD3110 23VA
MCD3132~MCD3500 40VA
MCD3600~MCD3800 55VA
The following range of auto-transformers are available
as optional accessories and can be fitted within the
MCD3000 where other control voltages must be used.
Part Number
Input Voltage
MCD3007 ~
MCD3055
MCD3075 ~
MCD3800
110 VAC / 460 VAC 175G5084 175G5144
110 VAC / 575 VAC 175G5085 175G5145
24 VAC / 110 VAC 175G5087 175G5146
Removing control voltage from the
MCD3000 resets the motor overload
protection.
Control wiring
The MCD3000 can be controlled using the local push
buttons, or via remote control inputs. Switch between
the local and remote modes using the
[LOCAL/REMOTE] push button.
The MCD3000 has four remote control inputs.
Contacts used for controlling these inputs should be
low voltage, low current rated (Gold flash or similar).
The Stop and Reset circuits must be closed for
the MCD3000 to run in remote control mode.
Push button control example:
Two wire control example:
ATTENTION
Simultaneously pressing the [STOP] and
[RESET] buttons causes the MCD3000 to
immediately remove voltage from the motor resulting in
a coast to stop. Any soft stop or D.C.Brake settings
are ignored.
Do not apply voltage to the control inputs.
The inputs are active 24 VDC and must
be controlled with potential free circuits.
The Par. Set input determines which of the two
MCD3000 motor parameter sets is operative. When a
start is initiated the MCD3000 checks the state of the
Page view 9