MCD3000 Series
8 MG.15.A4.22 - VLT is a registered Danfoss trademark
Installation
Either Relay Output C or Relay Output A can be
programmed to control operation of the bypass
contactor.
Par. 36 Relay A - Function Assignment = 1 (Run)
Par. 38 Relay C - Function Assignment = 0 (Run)
Failure to correctly connect the bypass
contactor (B1-T1, L2,-T2, & B3-T3) will
result in a loss of current based protection
systems possibly leading to a motor failure.
Failure to correctly connect the bypass
contactor (B1-T1, L2,-T2, & B3-T3) may
result in a phase to phase short circuit
causing severe equipment failure .
Power wiring - D.C.Brake connection
If the D.C.Braking function is to be used, a contactor
must be wired to short output terminals T2 & T3
during the braking operation. This contactor must be
controlled by the MCD3000 Relay Output C and Relay
Output C must be programmed for D.C.Brake
operation.
Refer to Par. 18 and 19 for D.C.Brake parameter
adjustments.
Refer Par. 38 Relay C - Function Assignment.
The MCD3000 power modules will be
damaged if the D.C.Brake contactor is
closed when the D.C.Brake function is not
operating, or if the .D.C.Brake contactor is incorrectly
connected between T1-T2 or T1-T3.
Power wiring – Inside delta connection
Models MCD3185 ~ MCD3800 can be connected
inside the delta circuit of the motor when fitted with an
optional Inside Delta Kit.
Soft starters connected within the delta circuit of a
motor control only phase current thereby enabling
them to be used with larger motors than would be
possible with normal line connection. See the
Specifications section of this manual for inside delta
ratings.
K1M
K1M Line Contactor
Legend
Motor
L3B
L1B
E
T2
L1
L2
L3
T1
T3
3 PHASE
SUPPLY
U1
V1
W1
U2
V2
W2
L2B
ATTENTION
For inside delta connection to be possible
both ends of all three motor windings must be
accessible.
When utilizing the inside delta connection
method voltage remains connected to one
end of the motor windings even when the
soft starter is in the off or tripped state. A