MCD3000 Series
= factory setting
MG.15.A4.22 - VLT is a registered Danfoss trademark 23
Pro
g
rammin
g
MCD3000 current read out with an external current
monitoring system.
ATTENTION
This adjustment affects all current based
functions. e.g. current read-out, motor
overload & all other current based protections and
current outputs.
Description of choice:
The gain should be adjusted according to the following
formula.
22 Serial Communications - Baud Rate
Value:
1 - 5
4 (9600 baud)
1 = 1200 baud
2 = 2400 baud
3 = 4800 baud
4 = 9600 baud
5 = 19200 baud
Function:
Sets the baud rate for serial communications.
Description of choice:
Set as appropriate.
23 Serial Communications - Satellite Address
Value:
1 - 99
20
Function:
Assigns the MCD3000 an address for serial
communications.
Description of choice:
Set a unique address number as appropriate.
24 Serial Communications - RS485 Time Out
Value:
0 - 100 seconds
0 seconds (Off)
Function:
Sets the maximum allowable period of RS485
inactivity.
Description of choice:
Set this parameter if it is required that a trip should
occur in the event of a failure of RS485
communications with the MCD3000.
A setting of 0 seconds allows the MCD3000 to
continue operating without regular RS485 activity.
ATTENTION
In the event of a RS485 Time Out trip the
MCD3000 cannot be reset until the RS485
communication is resumed. If the RS485
communications cannot be immediately re-established
and temporary manual control is required, Par 24
Serial Communications - RS485 Time Out must be set
to 0 seconds.
The MCD3000 includes two motor operating
parameter sets. Parameters 25 - 33 make up the
secondary parameter set and replicate the
primary parameter set, Parameters 1 - 9.
Refer to the Operation section of this manual for
detail on enabling the secondary parameter set.
25 Motor FLC
(Secondary Parameter Set)
Value:
(Depends On Model)Amps Depends on Model
See Par. 1 for Function & Description of choice.
26 Current Limit
(Secondary Parameter Set)
Value:
100% - 550% Motor FLC 350 %
See Par. 2 for Function & Description of choice.
27 Current Ramp - Initial Current
(Secondary Parameter Set)